For the finished Cat6A and fiber patch cords below, choose a self-laminating vinyl wrap sized to the jacket. The Cat6A wrap’s clear film wraps around the jacket to cover the marking. For an unterminated cable, consider a slip-on heat-shrink sleeve if it fits the jacket and the cable maker permits the required heat. If the sleeve needs an open end, slide it on before fitting the connector. Cat6A wrap specs · Fiber wrap specs · Brady’s guidance on marker location · Heat-shrink sizing and temperature guidance
Size and apply a vinyl wrap
Find the cable’s jacket outside diameter in the manufacturer specs. Pick a wrap whose published bundle diameter range includes that size. Diameter specifications for 596-12202 · Diameter specifications for 596-51896
| Patch cord | Published jacket diameter | Vinyl wrap with a matching diameter range |
|---|---|---|
| Vanco SCAT6A slim Cat6A | 3.5 ± 0.2 mm | HellermannTyton 596-12202, 2.54 to 4.32 mm |
| Corning F022201J1Z20002M LC fiber | 2 mm nominal | HellermannTyton 596-51896, 1.35 to 3.00 mm |
Both example wraps use thermal-transfer printing. For the fiber wrap in the table, print the ID and apply the label to a clean, dry section of the jacket free of dust and grease. Keep fingers off the adhesive. Place the printed section on the jacket, then wrap the clear portion around the jacket and over the print. Cat6A wrap specs · Fiber wrap application guidance · Brady’s self-laminating marker guidance
Size a heat-shrink sleeve
- Check both diameters. Compare the jacket diameter with the supplied and recovered diameters of the sleeve. HellermannTyton’s sizing guide
- Check the path onto the cable. If the sleeve must pass over a connector, check that its supplied diameter clears the connector. HellermannTyton’s sizing guide
- Check heat before applying it. The HST6-2WH sleeve has a published minimum shrink temperature of 90 °C. Corning separately lists an installation range of −20 °C to 70 °C for the fiber cord above. Check the cable maker’s guidance on applying heat to that cable before choosing a sleeve. The sleeve’s 2.2 mm maximum recovered diameter and the cord’s nominal 2 mm jacket diameter leave the fit unconfirmed. Choose the vinyl wrap for that cord because its published bundle diameter range includes the nominal jacket diameter. Sleeve specifications · Corning’s installation range · Fiber wrap specs
- Install the sleeve when heat is permitted. Print the HST6-2WH marker. For slip-on sleeves that need an open end, Brady recommends sliding the sleeve onto the cable before fitting the connector. Move the sleeve into position before shrinking. Follow the sleeve maker’s heating instructions. If using a heat gun, HellermannTyton advises working gradually from the middle toward one end, then from the middle toward the other. Work with ventilation, gloves, and safety glasses. Sleeve print specifications · Brady’s slip-on sleeve sequence · HellermannTyton’s hot-air guidance
Worked Cat6A sizing example. The HST6-2WH sleeve (553-50016) has a 6.0 mm minimum supplied diameter and a 2.2 mm maximum recovered diameter. As a preliminary jacket-diameter check, the Vanco jacket’s 3.3 to 3.7 mm range falls between those limits. Before choosing a sleeve, apply the sizing criterion in Tip 6 of HellermannTyton’s tubing guide. Sleeve dimensions · Vanco jacket specifications · HellermannTyton’s sizing guide, Tip 6
Evidence and limits. The Brady and HellermannTyton guides and the specifications for the parts listed above were checked on November 26, 2026. The applications were not tested.